Power Control Centre Vertical's PCC
Power Control Centre is used for distribution and control of various power source used in industry. Normally Power Control Centers is installed near power source hence fault level is high. It is designed to suit fault level of 50KA or 65 KA for 1 sec. Busbar system in Power Control Centers are designed to suit the fault level as well as temperature rise to 40°c above ambient. Ample space is provided for cable termination. Various protections like short circuit, overload, earth fault, under voltage etc are provided to protect source and equipment.
| Application | Specification |
| Type | Fixed/Draw out fully componential, dust and vermin proof |
| Rated Volatge | 600 V, 50 HZ, 3 phase, 4wire |
| Rated Frequency | 50Hz |
| Rated Current | Up to 6000A main busbar |
| Rated Short Circuit | STD 50 KA 1 sec , Optional 65 KA 1 sec |
| Bus bar Support | DOUGH MOULDING COMPOUND (DMC), SHIELD MOULDING COMPOUND (SMC) EPOXY RESIN, HYLAME SUPPORT |
| Bus bar Chamber | Aluminium / Copper, Electrolytic grade |
| Construction | CRCA 10 / 12 / 14 / 16 Guage as required. |
| Access | Single Front (Front) or Double Front ( Front & Rear) |
| Installation | With Space on Front as well as Rear |
| Cable Entry | Bottom or Top |
| Dimension of Section | Width – 600 / 800 / 1000 / 1200 / 1400mm / Height – 2250 / 2350 mm / Depth - 1000 / 1200 / 1400mm |
| Protection | IP 4X |
| Internal Partitioning | Form 3-B |
| Form of Separation | As per customer requirement |
| Ambient temperature | 40 degrees Celsius |